Gas Detector Calibration Message Handling Guide
This document provides step-by-step guidance on how to respond when the Gas Detection System displays the message "Calibration" on the main screen due to current output errors from the Gas Detector.
Step-by-Step Instructions
-
Log In to the Gas Detection System
-
On the main screen of the Gas Detection System, perform the login procedure using authorized credentials.
-
-
Enter I/O Setting Screen
-
Once logged in, tap “I/O-Setting” to activate the Setting screen.
-
-
Select the Affected Channel
-
On the Setting screen, identify the channel number showing the current deviation and tap the corresponding channel at the top of the screen.
-
-
Activate All Channel Settings
-
Tap the “ALL” checkbox at the top of the screen to select all related input/output settings.
-
-
Perform Zero Setting
-
Under the selected channel, tap “3.1 ZERO RANGE SET” to initiate Zero setting for calibration.
-
-
Save Settings
-
Press the “OK” button to save the configuration and exit the Setting screen.
-
-
Verify System Status
-
Return to the Main Screen of the Gas Detection System and confirm that the sensor displays correct and stable values.
-
⚠️ Important Notes
-
⚠️ Caution: Ensure the correct channel is selected before calibration to avoid setting errors.
-
⚠️ Warning: Do not power off the system during calibration as it may cause data loss or incomplete configuration.
Post-Configuration Verification
-
Confirm that the Calibration message disappears from the main screen.
-
Monitor the sensor values for a few minutes to ensure stability.