Overview
The DA-82 is a current signal output module that operates under RS-485 MODBUS RTU communication. It is used in industrial automation systems where an external master controller sends a command to generate a 4-20mA current output. The module is DIN rail-mountable and provides high accuracy signal conversion.
1. Safety Information (p.3-4)
- Electrical Hazards:
- Power must be isolated before installation or maintenance.
- This equipment operates at dangerous voltage levels, requiring extreme caution.
- Electrostatic Discharge (ESD) Precautions:
- Avoid static electricity discharges.
- Handle PCBs with care to prevent component damage.
- DO NOT remove or install PCBs while power is applied.
2. Storage Before Installation (p.5)
- Store the equipment in a dry, sheltered area to prevent environmental damage.
- Inspect all components for physical damage before installation.
- Verify that the equipment is not exposed to moisture or extreme temperatures.
3. Features (p.6)
- Generates a 4-20mA current output based on MODBUS RS-485 serial commands from the master controller.
- Supports multiple device addresses for parallel communication.
- MODBUS RTU protocol compliance, operating as a slave unit.
4. Technical Specifications (p.6)
Parameter |
Value |
Dimensions |
70W × 75H × 109.5D mm |
Material |
ABS, IP40 |
Accuracy |
±0.2% Full Scale (at 25°C ±5°C) |
Communication |
MODBUS RTU (RS-485) |
Baud Rate Options |
4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps |
Operation Temp. |
-5°C to +55°C (10-90% RH) |
Storage Temp. |
-20°C to +70°C (5-95% RH) |
Weight |
~230g |
Installation |
DIN Rail Mounting |
Output Current Range |
3.5-24mA (reliable operation range) |
5. Outline & Indicators (p.7)
- 8 output channels (each with 3 terminals).
- Requires a 24V DC power supply.
- LED Status Indicators:
- PWR (Power LED): Lit when power is supplied.
- RXD (Receive LED): Flashes when data is received.
- FAIL LED: Indicates an incorrect command or current out of range.
6. Installation & Communication Setup (p.8)
- DIP Switch Settings:
- Each device can be assigned a unique MODBUS slave address.
- Baud rate selection via DIP switch.
- RS-485 Communication Wiring:
- A/B terminals are used for data exchange.
- A 120Ω termination resistor is optional.
7. 4-20mA Signal Output & Power Options (p.9-10)
- Supports both external and internal power options for 4-20mA output.
- Jumper settings (JP1, JP2, JP3, JP4) define power supply mode:
- External Power Mode (Default): Uses independent power per channel.
- Internal Power Mode: Uses DA-82’s supply voltage for output generation.
- 4-20mA Interface Connection Examples provided in the manual.
8. MODBUS RTU Command & Data Structure (p.10-11)
- Master Controller Writing Commands:
- Uses 13-byte command packets for current output control.
- MODBUS Addressing Format:
- Each channel has a unique address and supports up to 8 channels per device.
- Example MODBUS Commands:
Output Current (mA) |
Data (Hex Code) |
Command Example |
3.5mA |
0x00 0x00 0x38 0x00 |
011000010002040000380021a3 |
4mA |
0x00 0x00 0x40 0x00 |
011000010002040000400003a3 |
8mA |
0x00 0x00 0x80 0x00 |
011000010002040000800053a3 |
16mA |
0x00 0x01 0x00 0x00 |
011000010002040001000063a3 |
20mA |
0x00 0x01 0x40 0x00 |
01100001000204000140005263 |
24mA |
0x00 0x01 0x80 0x00 |
01100001000204000180000263 |
9. Revision History (p.11)
- Version R4 (2025.03.03) – Fourth revision of the technical manual.