Overview
The HBI-100 is a signal processing unit designed for LED display dimming, 4-20mA signal conversion, and alarm output control. It features a high-performance 16-bit A/D converter and microprocessor, supporting 4 programmable alarm relay contacts (AL1, AL2, AL3, AL4) for monitoring applications.
1. Safety Information (p.3-4)
- Electrical Hazards:
- Ensure power isolation before installation or maintenance.
- The equipment operates at high voltage, requiring caution.
- Electrostatic Discharge (ESD) Precautions:
- Handle PCBs with care to prevent static damage.
- Use conductive packaging for PCB storage.
- DO NOT remove or install PCBs while power is applied.
2. Storage Before Installation (p.5)
- Store the equipment in a dry, covered area to protect from moisture and extreme temperatures.
- Inspect components for physical damage before installation.
- Ensure that packing cases are stored in a dry area to avoid water damage.
3. Features (p.6)
- 4-20mA current input signal processing.
- High-performance 16-bit A/D converter and microprocessor.
- 4 programmable alarm relay contacts (AL1, AL2, AL3, AL4).
- Dimming function for LED display adjustment.
- Hysteresis band configuration for stable alarm management.
- 30 linear section conversion for level-to-volume transformation.
4. Technical Specifications (p.6-7)
- Dimensions: 36(W) × 144(H) × 111.5(D) mm
- Material: ABS
- Accuracy: ±1% at 25°C ±5°C
- Measurement Period: 300ms
- Input Resistance: 68Ω (internal resistance for 4-20mA signals)
- Operating Temperature: -10°C to +50°C (10~90% RH)
- Storage Temperature: -20°C to +70°C (5~95% RH)
- Weight: 325g (approx.)
- Mounting: Panel mount
- Power Supply:
- 24V DC (18-32V range)
- Max Power Consumption: 5.04W (24VDC, Imax=220mA)
5. Layout & Panel Cut (p.7)
- Control Buttons:
- MODE: Used for settings.
- L/V: Switches between Level and Volume display modes.
- BS: Buzzer stop key & UP key in setting mode.
- DM: Dimmer control for LED lighting.
6. Connection & Power (p.8)
- 4-20mA Input Signal Processing:
- Converts input current to voltage signal via 68Ω resistor.
- Power Isolation:
- External power circuit and internal signal processing circuits are electrically isolated.
7. Main Functions (p.9-11)
- Scaling Function:
- Allows PV (process variable) scaling for custom display ranges.
- Alarm Delay Setting:
- Prevents false alarms by setting ON/OFF delay time (0-99 sec.).
- Input Transformation:
- Supports linear conversion of 4-20mA input to user-defined values.
- Zero & Span Adjustment:
- Provides manual correction for sensor offset values.
8. Operation & Configuration (p.11-12)
- Factory Mode: Pre-configured default settings for manufacturing.
- Setting Mode: Allows user customization for alarm setpoints, scaling, and delay times.
- Data Storage: Stores user settings in internal memory for non-volatile operation.
- Alarm Function:
- Volume-based alarm activation with adjustable delay settings.
9. Revision History (p.13)
- Version R1 (2025.03.03) – Initial release.