Overview
The HPI-100 is a pressure measurement and control unit designed to monitor tank pressure and convert it into tank level data. It communicates with a Master Unit via MODBUS RTU protocol and includes relay control functionality for solenoid valve operation.
1. Safety Information (p.3-4)
- Electrical Hazards:
- Always isolate power before installation or maintenance.
- High-voltage components are present; improper handling may lead to injury.
- Electrostatic Discharge (ESD) Precautions:
- Avoid static electricity discharges that can damage electronic components.
- Handle Printed Circuit Boards (PCBs) with care and use conductive packaging.
- DO NOT remove or install PCBs while power is applied.
2. Storage Before Installation (p.5)
- Store the equipment in a dry, sheltered area to prevent moisture and temperature damage.
- Before installation, check for:
- Bent or damaged components.
- Scratches, dents, or other physical deformities.
- Damaged connectors, leads, or PCBs.
3. System Description (p.6)
- The HPI-100 measures up to 24 tank pressures and converts them into tank levels.
- Equipped with a 24-bit A/D converter for high-precision measurements.
- Communicates via RS-485 MODBUS RTU protocol.
- Features relay control for solenoid valves.
- LCD Display shows real-time tank level readings.
4. Technical Specifications (p.6-7)
- Measurement Channels: 24 individual tank inputs.
- Accuracy: ±0.02mH₂O full scale.
- Power Supply: 24V DC (0.03A without relay/solenoid activation).
- Input Type Scaling: 0.000 ~ 42.000mA (mH₂O equivalent).
- Communication: RS-485, 2-wire (A, B), MODBUS RTU.
- Operating Temperature: -5°C to +55°C.
- Storage Temperature: -20°C to +70°C.
- Weight: Approx. 265g.
5. Configuration & Settings (p.8-13)
- MODBUS Slave Address Setting: Each HPI-100 unit must have a unique address (0x20 - 0xFF).
- Input Channel Number Setting: Supports up to 24 input channels.
- Relay Delay Time Configuration: Adjustable between 0 - 999 seconds.
- Password Management: Default 0000, user changeable.
- Back Pressure Compensation: Adjustable per channel (e.g., 10cmH₂O offset).
- Calibration: Factory pre-set, user adjustments not required.
- LCD Display Test & Brightness Adjustment: Ensures proper display functionality.
- Channel Hold Mode: Locks display to a single channel instead of auto-scrolling.
6. Communication Parameters (p.13-14)
- Baud Rate: 9600bps.
- Data Bits: 8-bit.
- Stop Bit: 1-bit.
- Parity: None.
- Supported MODBUS Commands:
- Read tank level.
- Adjust calibration settings.
- Modify relay control parameters.
7. Revision History (p.14-15)
- Version R4 (2025.03.03) – Fourth revision of the technical manual.