Overview
The DL-3100 Digital Output (DO) Module is an 8-channel relay output module designed for industrial automation systems. It features RS-485 MODBUS RTU communication, supporting remote operation and monitoring. Each output channel is electrically isolated, making it ideal for various control and signaling applications.
1. Safety Information (p.3-4)
- Electrical Hazards:
- Ensure power isolation before installation or maintenance.
- High voltage risks present; handle with care.
- Electrostatic Discharge (ESD) Precautions:
- Avoid static electricity discharges.
- Store and handle electronic components properly.
2. Storage Before Installation (p.5)
- Store in a dry, sheltered area to prevent environmental damage.
- Inspect all components for physical damage before installation.
3. System Description & Pin Assignments (p.6-7)
- Functionality:
- Provides 8 relay output channels (NC or NO configuration).
- Supports MODBUS RTU for seamless integration into industrial control systems.
- Features LED indicators for Power & Communication status.
- Pin Assignments:
- CH1 - CH8: Individual relay outputs with common (C) and output (O) terminals.
- RS-485 Communication Ports: Primary and auxiliary connections.
- 24V DC Power Input.
4. Installation & Wiring (p.8)
- Dry Contact Output Connection:
- Supports Normally Open (NO) and Normally Closed (NC) relay contacts.
- Power & Communication Connections:
- 24V DC power supply.
- RS-485 MODBUS RTU communication interface.
5. Communication & Data Handling (p.9-10)
- Supported Baud Rates:
- 1200, 2400, 4800, 9600, 38400, 57600, 115200.
- MODBUS Data Registers:
- Output Control: Enables remote switching of relay channels.
- Output Status Read: Retrieves the current state of relay outputs.
- Relay Contact Configuration: Allows customization of NO/NC operation per channel.
6. Technical Specifications (p.6)
- Power Supply: 24V DC, 3VA consumption.
- Output Channels: 8 relay contacts (NO or NC).
- Max Switching Capacity:
- 125VAC, 0.5A
- 24VDC, 1A
- Communication Interfaces:
- 2 x RS-485 MODBUS RTU.
- Environmental Conditions:
- Operating Temperature: 0°C to 70°C.
- Storage Temperature: -20°C to 70°C.
- Mechanical Data:
- Material: Aluminum, Chromate Coating.
- Dimensions: 105 × 27 × 74 mm.
- Protection Class: IP20.
7. Revision History (p.11-12)
- Version R2 (2025.03.01) – Second revision of the technical manual.