Overview
The MMCU-500C (Multi Monitoring Communication Unit) is a data communication and monitoring system that integrates multiple sensors, including level, temperature, and pressure transmitters. It processes and transmits data via RS-485 MODBUS protocol for marine and industrial applications.
1. Safety Information (p.5-6)
- Electrical Hazards:
- Power must be isolated before installation or maintenance.
- High voltage is present; ensure proper precautions.
- Electrostatic Discharge (ESD) Precautions:
- Avoid static electricity discharges.
- Store and handle electronic components properly.
2. Storage Before Installation (p.7)
- Store in a dry, sheltered area to prevent damage.
- Inspect all components for physical damage before installation.
3. System Description & Layout (p.9-11)
- Components:
- TLP-80MUX: Handles level, temperature, and pressure signals.
- AD-320: Converts 4-20mA signals into digital values.
- HTS-1308S & HTS-1308R: Convert HART signals to MODBUS RS-485.
- MMCU500CDI: TFT LCD display and communication interface.
- MMCU500CSP: Power supply module.
- Communication Protocol:
- Uses RS-485 MODBUS RTU for data exchange.
- Compatible with monitoring PCs and external control systems.
4. Installation & Commissioning (p.12-21)
- Installation:
- Mount in a dry, vibration-free location.
- Keep cables separate from high-voltage power lines.
- Electrical Connection:
- Power Supply: 24V DC input/output.
- Serial Ports:
- COM 1 & 2: Connect to level gauge systems.
- COM 3 & 4: Connect to monitoring computers.
- Commissioning Process:
- Verify power supply and communication LEDs.
- Perform sensor status checks.
- Backup configuration data before operation.
5. System Operation & User Interface (p.28-36)
- Home Screen: Displays real-time sensor data and alarms.
- Tank Monitoring:
- Supports Cargo, Ballast, and Fuel Tanks.
- Displays ullage, level, temperature, and pressure.
- Alarm indicators for High, Low, and Sensor Fail conditions.
- Event & Alarm History:
- Logs system faults, alarms, and configuration changes.
- Settings Menu:
- Tank Information: Configure alarm thresholds and offsets.
- Communication Settings: Adjust serial port configurations.
- Password Protection: Restrict access to critical settings.
6. Troubleshooting Guide (p.44-58)
- Incorrect Sensor Readings:
- Compare raw sensor values with expected data.
- Save communication logs for troubleshooting.
- Communication Port Failure:
- Check RS-485/422 DIP switch settings.
- Ensure unique COM port numbers are assigned.
- Tank Height Calibration Issues:
- Adjust Min/Max height settings in Tank Information Menu.
- Language & Time Settings:
- Switch between English and Korean via Regional Settings.
- Adjust local time settings under Control Panel.
- Software Reinstallation:
- Copy MMCU-500C program files from USB drive to Flash Disk.
- Restart the MMCU-500C unit.
7. Technical Specifications (p.27)
- Input Ports:
- 128 x 4-20mA input channels.
- 32 x HART communication channels.
- 32 x RS-485 communication channels.
- 24 x TLP-100S transmitters.
- Relay Outputs:
- System Fault, Data Alarm, Power Supply Fault, Sensor Error.
- Power Supply: 24V DC, 150VA consumption.
- Operating Temperature: 5°C to 70°C.
- Dimensions: 3U 19” Rack-mountable.
- Weight: 4.5 kg.