Overview
This document provides essential information for the PL40M-I-A Pressure Transmitter, including safety instructions, installation guidelines, operating conditions, troubleshooting, and maintenance. The PL40M-I-A is an intrinsically safe device, designed for accurate pressure and level measurement in hazardous industrial environments.
1. Safety Information (p.4-5)
- Electrical Hazards: Power isolation is mandatory before installation or maintenance.
- Intrinsic Safety Compliance: Certified for Ex ia IIC T6...T4 Ga (ATEX & IECEx standards).
- Electrostatic Discharge (ESD) Precautions:
- Avoid exposure to static electricity discharges.
- Store and handle electronic components properly.
2. Storage Before Installation (p.6)
- Store in a dry, covered area and keep in original packaging.
- Inspect for physical damage before installation.
3. Description and Application (p.9)
- The PL40M-I-A Pressure Transmitter measures gauge and absolute pressure in liquids.
- Suitable for process engineering applications, including tank level monitoring.
- Features hygienic connections, threaded connections, and diaphragm seals.
4. Technical Specifications (p.10-11)
- Measurement Ranges:
- Pressure measurement: 0 to 50 bar
- Burst pressure: up to 120 bar
- Operating Temperature:
- PL40M-I-A: -40°C to +85°C
- Protection Ratings:
- IP67 (dust and water-resistant).
- Output Signal: 4-20mA DC (2-wire system).
5. Mechanical Installation (p.12)
- Mounting Guidelines:
- Secure the transmitter using M42 x 1.5 threaded flange mounting.
- Ensure proper cable gland installation for environmental protection.
- Electrostatic Discharge (ESD) Risks:
- Install in locations protected from airflow that could cause charge buildup.
- Clean only with a damp cloth to prevent static accumulation.
6. Electrical Installation (p.13-14)
- Precautions:
- Ensure the power is OFF before making electrical connections.
- Connect transducer and power supply carefully, ensuring correct polarity.
- Intrinsic Safety Requirements:
- Must be used with an intrinsically safe isolation barrier or zener barrier.
- Certified for Zone 0, 1, and 2 applications.
7. Operation & Calibration (p.15)
- Startup Verification:
- 3.5mA output → No signal detected.
- 4-20mA output → Normal pressure reading.
- 21mA output → Overpressure condition.
- Calibration:
- Factory pre-set, but field adjustment may be required.
- Zero and Span calibration can be adjusted using the DIP switch and variable resistance.
8. Maintenance & Troubleshooting (p.16)
- Common Issues & Solutions:
- Indication Error → Adjust Zero/Span settings and check specific gravity.
- Zero Reading → Inspect power supply, isolation valve, and sensor status.
- Maximum Reading → Possible sensor failure—requires replacement.