1. Overview
The "CS301, Conductivity Too Low" alarm occurs when salinity falls below 10 PSU during Ballasting.
๐ When operating in low-salinity or freshwater areas, the A.P. Tank (Aft Peak Tank) must be pre-filled with seawater before starting Ballasting.
๐ If the A.P. Tank is not used for seawater storage, another designated W.B. Tank (Water Ballast Tank) may be used.
- Refer to the vessel's Piping Diagram to confirm the correct tank.
2. Preparation for Ballasting with the A.P. Tank
Step 1: Check BWTS Final Drawing (LOW SALINITY Section)
- Verify the BWTS Final Drawing (Low Salinity Section) for the correct flow path.
- Ensure the A.P.TANK is pre-filled with seawater before entering low-salinity or freshwater areas.
- Confirm that at least 1.2% of the total ballast capacity has been ballasted into the A.P.TANK in general seawater conditions.
- Confirm that at least 1.2% of the total ballast capacity has been ballasted into the A.P.TANK in general seawater conditions.
- In low-salinity/freshwater conditions, only seawater from the A.P.TANK should be supplied to the ECU (Electro Chlorination Unit) for electrolysis.
๐ Why?
Maintaining a proper seawater supply to the ECU ensures effective electrolysis in low-salinity environments.
Step 2: Valve Lineup (Refer to Piping Diagram)
- Close the EIP (ECU Inlet Port) valve to prevent freshwater inflow.
- Open the necessary valves to allow sea water from the A.P. Tank to supply the ECU.
๐ Why?
This configuration ensures that only seawater from the A.P. Tank is used for electrolysis instead of low-salinity water from the main pipeline.
3. Start Ballasting Using the A.P. Tank
- On the touchscreen BALLAST tab, press "START".
- Start ballasting using B/P (Ballast Pump).
- Monitor SYSTEM STATUS:
- Ensure CS301 (conductivity) exceeds 10 PSU.
- Check that FM301 (Side Flow Meter) reading is increasing.
๐ Why?
Proper conductivity levels confirm that sufficient salinity is present for electrolysis.
4. Air Venting (If FM301 Shows 0 mยณ)
If FM301 remains at 0 mยณ, perform air venting at the Strainer and EBP.
Step 1: Air Venting at the Strainer (If Installed Before EBP)
- Open the Strainerโs Air Vent Valve.
- Release air until a continuous seawater flow is observed.
- Close the air vent valve completely.
Step 2: Air Venting at the EBP
- Immediately after starting Ballasting, slightly loosen the EBPโs Air Vent Plug.
- Release air until a continuous seawater flow is established.
- Tighten the Air Vent Plug completely.
๐ Why?
Removing trapped air ensures consistent water flow through the system.
5. Exiting Low-Salinity or Fresh Water Areas
- Once the vessel moves into normal seawater regions, restore the valves to their original positions.
6. Summary of Key Actions
Checkpoint | Action |
---|---|
Check BWTS Drawing | Locate LOW SALINITY section |
Pre-Fill A.P. Tank | Ensure 1.2% of total ballast capacity is pre-filled with seawater using the system before Ballasting |
Configure Valves | Close EIP valve, open the valves connected from A.P. Tank |
Start Ballasting | On BALLAST tab, select START, then operate B/P |
Monitor Conductivity | Verify CS301 > 10 PSU, check FM301 flow rate |
Air Venting (If Needed) | Release air from Strainer's Air Vent Valve & EBP's Air Vent Plug |
Exit Fresh Water Areas | Restore valve configuration when returning to normal seawater |
Comments
0 comments
Article is closed for comments.