1. Overview
The "CS301, Conductivity too low" alarm occurs when the salinity level drops below 10 PSU during Ballasting.
📌 When operating in low-salinity or fresh water regions, the SCU (Salt Control Unit) must be used to prepare high-concentration saltwater, align the required valves, and ensure proper operation.
📌 SCU Installation Locations:
- Engine Room
- Upper Deck
2. SCU Preparation Steps
Step 1: Check SCU Tank Size
- Refer to the Final Drawing on board to confirm the SCU Tank size.
- The vessel’s BWTS manual provides saltwater preparation guidelines:
- For a 1m³ SCU Tank:
- 0.8m³ of fresh water
- At least 209kg of salt
- Can treat approximately 2,000m³ of ballast water
- For a 1m³ SCU Tank:
Step 2: Mix Salt and Water in SCU

(Example: SCU Tank Size = 1m³)
- Open the Freshwater Inlet Valve (CV108) and fill with 0.8m³ of fresh water, then close CV108.
- Close CV102 below SCU panel (upstream of SIP901).
- Open the Compressed Air Supply Valve (CV109) to aid in dissolving the salt.
- Move 209kg of salt (20kg x 11 bags) to the SCU Tank and pour it in.
- Supply compressed air for at least 1 hour to ensure complete dissolution of the salt.
- Once the salt is fully dissolved, close CV109 and open CV102.
📌 Why?
Salt must be fully dissolved before being injected into the Ballast system.
And the salt water have to be made before 3 days for Ballasting.
3. Valve Line-up for SCU Ballasting
-
Ensure that the following SCU panel valves are set correctly:
- CV101, CV102, CV103 must always remain OPEN.
- Select switch inside the SCU panel should always be set to AUTO.
- CV101, CV102, CV103 must always remain OPEN.
-
Open the SCU Outlet Valve located before the EBP(ECU Booster Pump) in the Engine Room.
-
Ensure the Sea Inlet Valve is always open.
📌 Why?
Proper valve alignment ensures correct saltwater injection into the Ballast system.
4. Start Ballasting Using SCU
- On the touchscreen BALLAST screen, press "START".
- When the "LOW SALINITY REGION?" pop-up appears, select "YES".
📌 Why?
Selecting YES activates SCU-assisted Ballasting.
5. Monitor System Status
- During Ballasting, monitor the SYSTEM STATUS screen:
- Ensure CS301 (conductivity) exceeds 10 PSU.
- Check that FM301 (Side Flow Meter) reading is increasing.
📌 Why?
A conductivity level must exceed at least 10 PSU to operate Ballasting.
6. Air Venting (If FM301 Shows 0 m³)
If FM301 remains at 0 m³, perform air venting at the Strainer and EBP.
Step 1: Air Venting at the Strainer (If Installed Before EBP)
- Open the Strainer’s Air Vent Valve.
- Release air until a continuous seawater flow is observed.
- Close the air vent valve completely.
Step 2: Air Venting at the EBP
- Immediately after starting Ballasting in BALLAST screen, slightly loosen the EBP’s Air Vent Plug.
- Release air until a continuous seawater flow is established.
- Tighten the Air Vent Plug completely.
📌 Why?
Removing trapped air ensures consistent flow through the SCU and Ballast system.
7. Exiting Low-Salinity or Fresh Water Areas
- Once back in normal seawater regions, close the SCU Outlet Valve to stop saltwater injection.
8. Summary of Key Actions
Checkpoint | Action |
---|---|
Check SCU Tank Size | Verify final drawing and confirm required salt & water volume |
Prepare Salt Solution | Add 0.8m³ water + 209kg salt, mix with compressed air for 1 hour (Example: SCU Tank Size = 1m³) |
Configure SCU Valves | Set CV101, CV102, CV103 to OPEN, ensure SCU select switch is in AUTO |
Open SCU Outlet Valve | Ensure SCU Outlet Valve is open, Sea Inlet valve remains open |
Start Ballasting | On BALLAST screen, select "YES" for LOW SALINITY REGION |
Monitor Conductivity | Verify CS301 > 10 PSU, check FM301 flow rate |
Air Venting (If Needed) | Release air from Strainer's Air Vent Valve & EBP's Air Vent Plug |
Exit Fresh Water Mode | Close SCU Outlet Valve when returning to normal seawater |
Comments
0 comments
Article is closed for comments.