1. Preparation
Ensure that you have the following materials before starting the procedure:
- VEGA CONNECT 4
- VEGA PACTware CD
- Notebook PC with administrative access
2. Installation of PACTware
- Insert the VEGA PACTware CD into the notebook PC.
- Follow the on-screen instructions to install the PACTware software.
- Ensure the installation completes successfully before proceeding.
3. Connection Setup
- Power Off the MMCU-500C
- Turn off the power switch located on the front cover of MMCU-500C.
- Connect VEGA CONNECT 4
- Retrieve the VEGA CONNECT 4 cable from its case.
- Connect one end of the VEGA CONNECT 4 to the barrier.
- Ensure a secure connection before proceeding.
4. Launching PACTware
- Start the PACTware Program
- Open the PACTware software from the notebook PC.
- Wait for the application window to load.
- Confirm Connection
- If an error message appears, verify the connections and restart the software.
5. Application Settings Adjustment
- Navigate to Application Settings in PACTware.
- Select Medium/Dielectric Constant
- Set the dielectric constant to "Chemical mixtures".
- Confirm Level Value
- Ensure the displayed level values are correct.
6. Final Check
- Review all settings before closing the software.
- Disconnect VEGA CONNECT 4 safely.
- Restore power to MMCU-500C.
Comments
0 comments
Please sign in to leave a comment.