Fault-15 Sensor Calibration Reset Manual Fault-15
1. Entering System Mode
- Press and hold the FUNC KEY for 2–3 seconds to enter SYSTEM MODE.
- Enter the password: [05] to proceed.
2. Accessing Factory Set Mode
- Press the FUNC KEY to navigate to FACTORY SET MODE.
- Use the ▲ (Up) and ▼ (Down) keys to select the SENSOR option.
3. Sensor Initialization
- Proceed with the sensor initialization process.
- After initialization, reapply power to the system.
- A SELF TEST will run for 15 minutes automatically.
4. AGC Initialization
- Re-enter FACTORY SET MODE within SYSTEM MODE.
- Use the ▲ (Up) and ▼ (Down) keys to select AGC.
- Proceed with the AGC initialization and reapply power.
- The system will perform another 15-minute SELF TEST.
5. Final Steps
- All calibration-related data have now been reset.
- Recalibrate the system as needed and verify if the issue has been resolved.
Caution:
- Ensure proper power cycling after each initialization step.