This manual provides the procedure for adjusting the Vapour Pressure range settings in the OVMS-50 alarm unit.
1. Adjusting the Measurement Range
Follow these steps to configure the Vapour Pressure range:
-
Access the Alarm Unit Settings
- Press the "M" key on the alarm unit.
-
Select the Channel
- Choose Channel 3 and press the Enter key until the channel setting menu appears.
-
Enter Password
- Input the password: "0000" and confirm.
-
Modify the High Scale Setting
- Use the Arrow button to navigate.
- Set the High Scale value to 0.200.
-
Save and Exit
- Press the "Go Back" button multiple times to return to the operating mode.
2. Final Verification
- Confirm the High Scale setting is correctly applied.
- Check the Vapour Pressure readings to ensure they are within the expected range.
- If any issues persist, verify sensor connections and calibration settings.
3. Troubleshooting Notes
- If the alarm still shows incorrect values, check the sensor input signal.
- Ensure that all cable connections are properly secured.